Volume 14, Issue 3 (2017)                   ioh 2017, 14(3): 37-45 | Back to browse issues page

XML Persian Abstract Print


Download citation:
BibTeX | RIS | EndNote | Medlars | ProCite | Reference Manager | RefWorks
Send citation to:

Kariznovi H, Farshad A A, Yarahmadi R, Khosravi Y, Yari P. Consequence Analysis of fire and explosion of a cylindrical LPG tank in a selected industry of oil and gas . ioh 2017; 14 (3) :37-45
URL: http://ioh.iums.ac.ir/article-1-1714-en.html
, fdgir@yahoo.com
Abstract:   (6696 Views)

Background and aims: Accidents happened as a result of LPG leakage emphasizes the importance of the consequence analysis of fire and explosion in LPG storage tanks. The purpose of this study is to analysis the consequences of fire and explosion in a cylindrical LPG storage tank in an oil and gas industry.

Method: In this analytical study, four possible failure scenarios including 1) rupture in the cylindrical LPG tank 2) leakage from the loading line 3) leakage from the tank manhole and 4) undesirable opening of the safety valve, and their fire and explosion consequences were simulated by PHAST software. Then the results were compared with existing standards

Results: The scenario of tank rupture leads to a radiation flux 37.5 kw/m2 affect a radius of 290 m from tank location that can cause major life and property losses. As the result of a flash fire due to the tanker rupture, there is a possibility of life-threatening to a radius of 520 m. An explosion (resulting from the tank rupture) with blast wave of 0.2 bar affect a radius of 2092 m that can cause the life and property losses. The scenario of leakage from the tank manhole leads to jet fire, explosion and flash fire. Also, the jet fire and flash fire will follow by the scenarios of leakage from the loading and undesirable opening of the safety valve.

Conclusion: With attention to severity the tank rupture and the likelihood of occurrence of the domino effect, it is recommended to substitute the horizontal cylindrical LPG tanks by the spherical ones. Also, an emergency response plan should be established based on the result of this study.

Keywords: Consequence Analysis, Fire, Explosion, LPG Tank, PHAST

Full-Text [PDF 554 kb]   (4610 Downloads)    
Type of Study: Applicable | Subject: Process Safety
Received: 2016/01/15 | Accepted: 2016/06/8 | Published: 2017/07/11